Customer: Phanteks
Axpertec B.V. Sydneystraat 33, 3047BP, Rotterdam, The Netherlands

M25-120 G2

Report Number: 25FN182A
Customer ID: 83
Lab ID: PH12000182

Test Report Results

Section A: Noise Testing Equipment

Test Environment Hemi-Anechoic Chamber with 6 dB(A) noise floor
Conditions 25(±2) degrees Celsius, 40-50% humidity
Sound Analyzer Bruel & Kjaer 2270-S G4 & 2250-L G4
Microphone Bruel & Kjaer Type 4955-A
Mic Calibrator Bruel & Kjaer Type 4231
Data Logger Picoscope TC-08
Testing Methodology Cybenetics Phi Fan Performance Standard

Section B: Fan Testing Equipment Technical Specifications

Manufacturer Long Win Science & Technology Corporation
Model Number LW-9266
Air Flow Rate 2.4 – 250 CFM
Accuracy of Air Flow Rage < 3.5% INFS
Repeatability error < 2%
Static pressure 0-20mmAq (100mmAq with the high static pressure throttle device)
Overall Dimensions 0.7 (W) x 2.2 (L) x 1.6 (H) m
Power Source 220VAC, 5A, Single Phase, 50/60Hz
Based on Standards ISO 5801-2007, AMCA 210-0, ASHRAE 51-2007, IEC 61591-2005, GB/T 1236-200

Section C: PHI Performance Levels

25dBAP Max1.17
25dBAQ Max49.81

Section D: Information about DUT

Model NamePhanteks
Serial Number886523003465
Lab IDPH12000182
Comments
Date of receiptApr 5, 2025
Report Issued DateMay 20, 2025
Testing DateMay 20, 2025
Engineer NameGeorgios Theodoros Sarimpalas
Authorized By the Laboratory General ManagerAristeidis Bitziopoulos
Signature

Section E: Deviation Additions, deviations, and exceptions to the method table

Fan Performance - Static Pressure

The Fan Static Pressure Measurement’s Uncertainty is ±0.68 Pa

The reported expanded uncertainty (U) was derived as the product of the combined standard uncertainty (u) and the coverage factor k = 2, corresponding to a confidence interval of approximately 95%. Measurement uncertainty was determined in accordance with JCGM Guide 100:2008, "Guide to the Expression of Uncertainty in Measurements". The estimate of the reported uncertainty pertains to values obtained during the measurements and does not account for possible long-term changes.

Static Pressure Uncertainty Budget

Source of Uncertainty Standard Uncertainty, u(xi) (Pa)
LW-9266 Instrument Accuracy 0.260
Repeatability 0.075
Calibration 0.012
Temperature influence 0.208
Relative Combined Standard Uncertainty (RSS): 0.34
% Expanded Uncertainty U (k=2, norm): 0.68
Fan Performance - Airflow

The Fan Airflow Measurement’s Uncertainty is ±3.94 CFM

The reported expanded uncertainty (U) was derived as the product of the combined standard uncertainty (u) and the coverage factor k = 2, corresponding to a confidence interval of approximately 95%. Measurement uncertainty was determined in accordance with JCGM Guide 100:2008, "Guide to the Expression of Uncertainty in Measurements". The estimate of the reported uncertainty pertains to values obtained during the measurements and does not account for possible long-term changes.

Fan Airflow Uncertainty Budget

Source of Uncertainty Standard Uncertainty, u(xi) (CFM)
Repeatability 1.750
LW-9266 calibration 0.600
Environmental variation 0.500
Position error 0.482
Relative Combined Standard Uncertainty (RSS): 1.97
% Expanded Uncertainty U (k=2, norm): 3.94